ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
62
3.2.4
Parameter window
Enable Outputs A-D
In this parameter window
Outputs A-D
can be enabled.
Note
In the following the setting possibilities of
Outputs A-D
are explained using
output A as an example.
The setting possibilities for outputs A-D are identical.
Output A
(20 A/16 AX C-Load)
Options: disabled
enable
•
disabled:
Output A (20A/16AX)
is blocked/invisible, no communication
objects are visible.
•
enable:
The parameter window
A: Output (20 A/16 AX)
appears.
Dependent communication objects become visible.
Designation
Options:
- - - TEXT - - -
With this parameter it is possible to enter a text of up to 40
characters in length for identification in the ETS.
Note
The text which is entered is used to provide help, in order to obtain
an overview of the inputs when they are fully assigned and to
indicate the function assigned to the input.
The text is purely for informative purposes and has no further
function.