Reaction on bus voltage recovery
Options: unchanged
UP
DOWN
STOP
This parameter defines how the output should respond with bus voltage
recovery.
•
unchanged:
The current state is retained.
•
UP/DOWN/STOP:
A fixed relay contact position is set.
Position after reference movement
Options: deactivated
no
reaction
move to saved position
This parameter enables the
Reference movement
communication object and
defines how the Room Master responds after a reference movement.
For further information see: Communication objects
page 200
•
deactivated:
The communication object
Reference movement
is not
visible. No referencing can be performed.
•
no reaction:
The shutter remains either up or down in the reference
position after the reference movement.
•
move to saved position:
The shutter is retracted to the position in which
it was before the reference movement was performed.
If the automatic function was activated for the shutter before the
reference movement, then the function is re-activated again
automatically after the stored position is reached.
Note
If during a reference movement a direct or automatic movement of
position command is received, then the reference movement is performed
first and the received target position is approached afterwards.
For further information see:
Determination of the current position
, page 227
Position of louvre after arriving
on lower end position
Options:
100 % (deactivated)
0
90 %
…
0
10 %
00
0 %
After the shutters are moved to the end positions the louvres are normally
closed. The louvre positions can be set via this parameter as the Room
Master is set after the lower end position is reached.
The parameter relates to the reaction of the shutter, if the motion has been
triggered via the communication object
Shutter/Blinds UP/DOWN move
or
by the
Automatic
function.