![ABB i-bus KNX Room Master Premium RM/S 2.1 Product Manual Download Page 110](http://html.mh-extra.com/html/abb/i-bus-knx-room-master-premium-rm-s-2-1/i-bus-knx-room-master-premium-rm-s-2-1_product-manual_3076110.webp)
ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
108
3.2.6.2.1 Parameter window
K: Blinds
- Drive
In this parameter window the settings for the blind drive are undertaken.
This parameter is visible if in parameter window
,
Blinds
has been selected with parameter
Output K
(Shutter) (6 A)
.
Total travel time
in s [1…18,000]
Options: 1…60…18,000
This parameter defines the total travel time from the upper end position to
the lower end position.
Reversing time in ms [50…5,000]
(see techn. data of the drive!)
Options: 50…700…5,000
This parameter defines the duration of the minimum reversing time between
two directions of motion.