ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
190
No.
Function
Object name
Data type
Flags
46 Switch
Input
a:
Switch/dim sensor
EIS 1, 1 bit
DPT 1.001
C, W, T
This communication object is enabled if in the parameter window
Enable inputs a-f
the parameter
Input a (binary input, contact scanning)
has been selected with the option
Switch/Dim sensor
.
In accordance with the parameter setting, this communication object can be switched by
actuation of the input to ON, OFF or TOGGLE.
With toggle the previous value, e.g. 1, is toggled directly to the value 0.
With parameter setting
TOGGLE
the communication object as the non-sending group address
should be linked with the switch feedback of the dimming actuator (updating of the switching
state).
Note
The communication object can be written to externally. Thus cyclic sending
is interrupted or may not be possible depending on the parameter setting.
No further communication objects are visible with the setting.
Telegram value:
0 = OFF
1 = ON
47 Dimming
Input
a:
Switch/dim sensor
EIS2, 4 bit
DTP 3.007
C, T
This communication object is enabled if in the parameter window
Enable inputs a-f
the parameter
Input a (binary input, contact scanning)
has been selected with the option
Switch/Dim sensor
.
A long operation at the input has the effect that
BRIGHTER
or
DARKER
dim commands are
sent via this communication object on the bus. A STOP command is sent and the cyclic
sending of dim commands is stopped at the end of actuation with START-STOP-DIMMING.
48
Not assigned.
49