Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
71
Restart of staircase time after end of
permanent ON
Options: no
yes
•
no:
The lighting switches off if
Permanent ON
is ended.
•
yes:
The lighting remains on and the staircase lighting time
restarts.
The function of continuously ON is controlled via the
Permanent ON
communication object value. If the communication object receives a
telegram with the value 1, the output is switched ON irrespective of
the value of the communication object
Switch
and remains switched
on until the communication object
Permanent ON
has the value 0.
Value object "function time disable"
on bus voltage recovery
Options:
unchanged
1, i.e., function time disable
0, i.e., function time enable
This parameter defines how the time function parameter should
behave after bus voltage recovery. With a telegram to the
communication object
Disable function time
the function time can be
disabled.
•
unchanged:
The function time can continue unchanged.
Note
The state
Function time
is stored with bus voltage failure and
continues unchanged after bus voltage recovery.
•
1, i.e., function time disable:
The time function is disabled by
a telegram with the value 1.
Note
They can only be enabled via the communication object
function
time disable
.
•
0, i.e., function time enable:
The
Function time
is enabled by
a telegram with the value 0.
Note
If the staircase light is disabled when the function
time
is
operational, the light will stay at ON until it is switched to OFF
manually.
How does the staircase light behave with bus voltage failure?
The behaviour at bus voltage failure is determined by the parameter
Reaction on bus voltage failure
in the parameter window
A: Output
(20 A/16 AX C-Load)
.