ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
57
Inactive wait state after bus voltage
recovery in s [0…30,000]
Options: 0…30,000
Here the waiting time after a bus voltage recovery is set. After the
waiting time has elapsed the state on the input terminals is scanned.
The input reacts as if the state on the input terminals has just
changed.
Note
The inactive waiting time does not add to the actual, adjustable
send delay time. This can be set separately.
Value 1 (rising edge/
short operation)
Options:
do not send
1 bit value [0/1]
2 bit value [forced operation]
1 byte value [-128…127]
1 byte value [0…255]
1 byte value [8 bit scene]
2 byte value [-32,768…32,767]
2 byte value [0…65,565]
2 byte value [EIB floating point]
3 byte value [time of day, weekday]
4 byte value [-2,147,483,648…2,147,483,647]
4 byte value [0…4,294,967,295]
This parameter serves for defining the data type which is sent when the
contact is actuated.
Depending on the selection made in parameter
Value 1
(rising edge/short
operation)
, different parameters appear. All parameters are described in the
following:
sent value [X]
Options: 0/1
-128…0…127
0…255
-32,768…0…32,767
0…65,535
-100,00…20,00…100,00
-2,147,483,648…0…2,147,483,647
0…4,294,967,295
This parameter defines the value which is sent on actuation.
The value range is dependent on the set data type of the value X.
sent value
Options:
ON, activate forced operation
OFF, activate forced operation
Disable forced operation
This parameter defines the value which is sent on actuation.