ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
194
No.
Function
Object name
Data type
Flags
46
Value 1
Input a:
Value/forced operation
EIS variable
DPT variable
C, T
This communication object is enabled if in the parameter window
Enable inputs a-f
the parameter
Input a (binary input, contact scanning)
has been selected with the option
Value/forced operation
.
This communication object sends a value on the bus with short operation when opening or
closing of the contact. The value and data type can be freely set in the parameters.
1 bit value [0/1 ]
2 bit value [0…3]
1 byte value [-128…127]
1 byte value [0…255]
1 byte value [8 bit scene]
2 byte value [-32.768…32.767]
EIS 1
EIS 8
EIS 14
EIS 6
EIS 6
EIS 10
DPT 1.001 switch command
DPT 2.001 forced operation
DPT 6.010 value
DPT 5.010 value
DPT 18.001 control scene
DPT 7.001 value
2 byte value [0…65,535]
2-byte value [EIB floating point]
3 byte value [time of day, weekday]
4 byte value [0…4.294.967.295]
EIS 10
EIS 5
EIS 3
EIS 11
DPT 8.001 value
DPT 9.001 temperature
DPT 10.001 time of day, weekday
DPT 12.001 value
4 byte value [-2,147,483,648…2,147,483,647] EIS 11
DPT 13.001 value
47
Value 2
See communication object 46.
48…
49
Not assigned.