Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
109
Outputs are disconnected from voltage after
Options:
End po no overflow
End po 2 % overflow
End po 5 % overflow
End po 10 % overflow
End po 20 % overflow
Total travel time + 10 % Overflow
•
End position…:
The application program calculates the movement time
required from the current position to the end position. After the end
position has been reached (as the very top or bottom), the shutter drive
will switch off independently. A so-called “Overload” can be set to ensure
that the Room Master safely reaches the end position. Thus the voltage
still remains applied for a short time to move the drive to a defined end
position in a controlled manner.
•
Total travel time + 10 % Overflow:
The shutter drive is always activated
for the set total movement time + 10 % independently of the current
position of the shutter.
For further information see:
, page 224