3.3.2.2.4
Output A,B: Switch actuator - Logic parameter window
All settings for the
Connection/Logic
function are undertaken in this parameter window.
It is visible if the
Enable function Connection/Logic
parameter is enabled in the Output A,B: Switch actuator
The
Connection/Logic
function provides up to two connection group objects for each output, which can be
logically connected with the
Switch
group object.
The logic is always re-calculated when a group object value is received. First, the
Logical connection 1
group object is evaluated by the
Switch
group object. The result is then logically connected by the
Logical
connection 2
group object.
Explanations of the Logic function are provided in Connection/logic, p. 131. Please also note the Function
diagram, p. 126, from which the priorities are derived.
Logical connection 1 active
Options:
No
Yes
This parameter enables the
Logical connection 1
group object.
•
Yes
: The following parameters appear:
Function of logical connection
Options:
AND
OR
XOR
GATE
The logical function of the
Logical connection 1
group object is determined by the Switch telegram.
All three standard operations (AND, OR, XOR) are possible. In addition, the GATE operation can
be used to inhibit switch commands.
For further information see: Connection/logic, p. 131
Result is inverted
Options:
No
Yes
•
Yes
: The result of the logical connection can be inverted.
•
No
: There is no inversion.
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......