ABB i-bus
®
KNX
Planning and application
136 2CDC506083D0201 | JRA/S 6.230.3.1
Inputs
•
The inactive waiting time is only active on bus voltage recovery.
Blind
The reaction of the blind/shutter output is parametrizable. The output can assume any state or remain
unchanged.
Note
The position of the blind or shutter is also stored in the event of bus voltage failure if the
Automatic
function is activated. The blind or shutter remains in the same position.
On bus voltage recovery, the position is retained and the group object value is undefined. The value is
not updated until the next Move telegram.
If the
Activation of autom. control
group object has not been assigned a group address, the
Automatic
function is deactivated when there is a download.
If Automatic is active, it remains on after a download until the next manual override or until it is
deactivated by the
Activation of autom. control
group object.