ABB i-bus
®
KNX
Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 107
No.
Function
Object name
Data type
Flags
77
Disable function Time
Output A
1 bit
DPT 1.003
C, W
This group object is enabled if the
Enable function Time
parameter is set to
Yes
in the
Output A,B: Switch actuator
parameter
window.
The group object value on bus voltage recovery can be set using the
Object value "Disable function Time" on bus voltage
recovery
parameter in the
- Time
parameter window.
With the Time function disabled, the output can only be switched on or off; the
Staircase lighting
function is not triggered.
Telegram value
1 = staircase lighting disabled
0 = staircase lighting enabled
The contact position at the time of disabling and enabling is retained and will only be changed with the next switch telegram
to communication object
Switch
.
78
Scene
Output A
1 byte
DPT 18.001
C, W
This group object is enabled if the
Enable function Scene
parameter is set to
Yes
in the
Output A,B: Switch actuator
parameter
window.
Using this 8-bit group object, a Scene telegram can be sent using a coded telegram. The telegram contains the number of the
scene concerned as well as the information on whether the scene is to be recalled or if the current contact position is to be
assigned to the scene.
Telegram format (1 byte): MXSSSSSS
(MSB) (LSB)
M: 0 – scene is recalled
1 – scene is stored (if allowed)
X: not used
S: scene number (1-64: 00000000…00111111)
KNX 1 byte telegram value
Meaning
Decimal
Hexadecimal
00 or 64
01 or 65
02 or 66
…
63 or 127
00h or 40h
01h or 41h
02h or 42h
…
3Fh or 7Fh
Recall scene 1
Recall scene 2
Recall scene 3
…
Recall scene 64
128 or 192
129 or 193
130 or 194
…
191 or 255
80h or B0h
81h or B1h
82h or B2h
…
AFh or FFh
Store scene 1
Store scene 2
Store scene 3
…
Store scene 64
For further information see: Scene function, p. 133 and Code table, 8 bit scene, p. 142
79
Forced operation
Output A
1 bit
DPT 1.003
C, W
This group object is enabled if the
Enable function Forced operation
parameter is set to
Yes
and the
Object type “Forced
operation”
parameter is set to
1 bit
in the
Output A,B: Switch actuator
parameter window.
If this group object receives the value 1, the output is forcibly set to the parametrized switch position set in the
Output A
parameter window. The forced positioning of the contact continues until forced operation ends, which it does when a 0 is
received via the
Forced operation
group object.
Please note that the
Forced operation
function and a bus voltage failure have a higher priority on the contact position,
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......