ABB i-bus
®
KNX
Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 101
3.4.3.2
Switch/dimming sensor group objects
No.
Function
Object name
Data type
Flags
10
Block
Input a:
Switch/dimming sensor
1 bit
DPT 1.003
C, W
This group object is enabled if the
Enable group object "Block" 1 bit
parameter is set to
Yes
in the
Input a: Switch/dimming
sensor
parameter window.
Using the communication object
Block
, the input can be blocked or enabled. With activated communication object
Block
the
inputs are blocked.
Note
When the input is blocked there is fundamentally no reaction to a signal change on the input, but:
– Waiting for a long button operation or a minimum signal duration is suspended.
– Parametrized
Cyclic sending
is interrupted with dimming steps.
– It is still possible to write the
Switch
group object.
When enabling an input, a change of the signal states (as opposed to before the block) leads to immediate
processing, e.g.:
– The minimum actuation or detection of a long/short button push starts.
– Group objects send their value if necessary.
Telegram value:
0 = enable input a
1 = Block input a
11
Switch
Input a:
Switch/dimming sensor
1 bit
DPT 1.001
C, W, T
This group object is enabled if the
Function
parameter is set to
Switch/dim sensor
in the
Input a
:
Function
parameter window.
In accordance with the parameter setting, this group object can be switched by actuating the input to
ON, OFF
or
TOGGLE
or
can be set to
No reaction
. With toggle, the previous value, e.g. 1, is toggled directly to the value 0. With the TOGGLE setting,
the group object should be linked with the switch feedback of the dimming actuator (updating of the switching state) via a non-
sending group address.
Note
The communication object can be written to externally. Thus cyclic sending is interrupted or may not be possible
depending on the parameter setting.
No further group objects are visible with the setting.
Telegram value:
0 = OFF
1 = ON
12
Dimming
Input a:
Switch/dimming sensor
4 bit
DPT 3.007
C, T
This group object is enabled if the
Function
parameter is set to
Switch/dim sensor
in the
Input a
:
Function
parameter window.
A long operation at the input has the effect that BRIGHTER or DARKER dim telegrams are sent via this communication object
on the bus. A STOP telegram is sent and the cyclic sending of dim telegrams is stopped at the end of actuation with START-
STOP-DIMMING.
13, 14
Not assigned
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......