Position for sun = 1 (sun)
Options:
No reaction
UP
DOWN
STOP
Receive position via 8-bit values
This parameter defines the reaction for sun = 1 (sun) in automatic sun protection mode.
•
No reaction
: The current movement is completed.
•
UP
: The blind moves UP.
•
DOWN
: The blind moves DOWN.
•
STOP
: The output is electrically disconnected, i.e. a moving blind is stopped.
•
Receive position via 8-bit values
: The blind moves to the position by receiving an 8-bit value from
group objects
Move to pos. for sun [0..255]
or
Adjust slat for sun [0...255]
.
Delay for sun = 1
in s [0...65,535]
Options:
0…60…65,535
This parameter defines the delay on activation of
Position for sun = 1
.
Via this parameter you can, for example, prevent the blind moving UP and DOWN if the sun is only
overcast for a short period of time.