Commissioning
110 2CDC506083D0201 | JRA/S 6.230.3.1
No.
Function
Object name
Data type
Flags
78
Adjust slat
Blind Output A,B
1 byte
DPT 5.001
C, W, T
This group object is enabled if the
Mode Output
parameter is set to
Blind
in the
Output A,B: Mode
parameter window.
This group object is used for movement to and feedback of a defined slat position and is therefore only available in Blind
mode.
If this group object receives a telegram, the slats are positioned in accordance with the received value. If the blind is currently
moving, the movement will continue to the target position before the slats are positioned.
Telegram value:
0
= slats fully OPEN
…
= Intermediate position
255 = slats CLOSED
79
Reference movement
Blind Output A,B
Shutter Output A,B
1 bit
DPT 1.008
C, W
This group object is enabled if the
Mode Output
parameter is set to
Blind
in the
Output A,B: Mode
parameter window.
This group object is used to compensate for position deviations, e.g. after frequent UP/DOWN movements to intermediate
positions. The blinds are moved to the end position (0 = upper, 1 = lower) and back.
If this group object receives a telegram the blind is moved fully upwards or downwards.
The current position is stored in order to move the blind to the parametrized position after the reference movement.
If the option
Back to stored position
is set and the
Automatic
function was set for the blind before the reference movement,
it is reactivated after the stored position is reached.
Telegram value:
0 = reference movement fully upwards
1 = reference movement fully downwards
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......