ABB i-bus
®
KNX
Planning and application
128 2CDC506083D0201 | JRA/S 6.230.3.1
4.2.2.1
Staircase lighting
After the staircase lighting time T
ON
has elapsed, the output switches off automatically. For every telegram
with the value 1 the time restarts (
Retrigger
function) unless the parameter
Extending staircase lighting by
multiple switch on ("Pumping up")
in the Output A,B: Switch actuator - Time parameter window, p. 42 is set
to
No (not retriggerable)
.
This reaction is the basic reaction of the
Staircase lighting
function.
Via "pumping up" – operation of the push button several times in succession – users can adapt the
staircase lighting to current needs. The maximum duration of the staircase lighting time can be set in the
parameters.
If the device receives a further ON telegram while the staircase lighting is switched on, the staircase
lighting time is added to the remaining period.