![ABB i-bus KNX JRA/S 6.230.3.1 Product Manual Download Page 31](http://html.mh-extra.com/html/abb/i-bus-knx-jra-s-6-230-3-1/i-bus-knx-jra-s-6-230-3-1_product-manual_3075031.webp)
ABB i-bus
®
KNX
Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 29
3.3.2.1.2
Output A,B: Blind - Automatic parameter window
This parameter window is used to make settings for the
Automatic
function. It is visible if the
Enable function Automatic
parameter is set to
Yes
in the Output A,B: Blind parameter window, p. 22.
The
Automatic
function enables simple automatic sun protection, and automatic protection against dazzle
in conjunction with the Shutter Control Unit.
For further information see: Automatic sun protection, p. 120 and Output A,B: Blind and Shutter group objects, p. 109
Deactivation by direct operation
Options:
No
Yes
This parameter defines how the
Automatic
function is deactivated: via either the
Activation of autom.
control
group object or via
direct operation
.
Note
The position of the blind or shutter is also stored in the event of bus voltage failure if the
Automatic
function is activated. The blind or shutter remains in the same position.
On bus voltage recovery, the position is retained and the group object value is undefined. The value is
not updated until the next Move telegram.
If the
Activation of autom. control
group object has not been assigned a group address, the
Automatic
function is deactivated when there is a download.
If Automatic is active, it remains on after a download until the next manual override or until it is
deactivated by the
Activation of autom. control
group object.
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......