![ABB i-bus KNX JRA/S 6.230.3.1 Product Manual Download Page 24](http://html.mh-extra.com/html/abb/i-bus-knx-jra-s-6-230-3-1/i-bus-knx-jra-s-6-230-3-1_product-manual_3075024.webp)
ABB i-bus
®
KNX
Commissioning
22 2CDC506083D0201 | JRA/S 6.230.3.1
3.3.2.1
Output A,B: Blind parameter window
All settings for Output A,B
: Blind
are undertaken in this parameter window. It is visible if the
Operation mode
parameter is set to
Blind
in the Output A,B Operation mode parameter window, p. 21.
Reaction on bus voltage failure
Options:
Unchanged
UP
DOWN
STOP
The output can assume a defined state on bus voltage failure via this parameter.
•
Unchanged:
The relay position of the outputs does not change. Any movements in progress are
therefore performed to completion.
•
UP/DOWN/STOP:
Sets a fixed relay contact position.
Note
If the relay has been switched immediately before a bus voltage failure, it may not be possible
to implement the options
UP
and
DOWN
.
The power stored in the Blind/Roller Shutter Actuator is not sufficient for this.
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......