![ABB i-bus KNX JRA/S 6.230.3.1 Product Manual Download Page 46](http://html.mh-extra.com/html/abb/i-bus-knx-jra-s-6-230-3-1/i-bus-knx-jra-s-6-230-3-1_product-manual_3075046.webp)
ABB i-bus
®
KNX
Commissioning
44 2CDC506083D0201 | JRA/S 6.230.3.1
Staircase lighting starts after
permanent ON is ended
Options:
No
Yes
•
No
: The lighting switches off if
Permanent ON
is ended.
•
Yes
: The lighting remains on and the staircase lighting time restarts.
The function of Permanent ON is controlled via the
Permanent ON
communication object value.
If the communication object receives a telegram with the value 1, the output is switched on
regardless of the value of the communication object
Switch
and remains switched on until the
communication object
Permanent ON
has the value 0.
Object value "Disable function Time"
on bus voltage recovery
Options:
Unchanged
1, i.e., disable function Time
0, i.e., enable function Time
This parameter defines how the
Time
function should react after bus voltage recovery.
The
Time
function can be disabled with a telegram to the
Disable function Time
group object.
•
Unchanged:
The
Time
function continues unchanged.
Note
The state of the
Time
function is stored on bus voltage failure and continues unchanged after
bus voltage recovery.
•
1, i.e., disable function time
: A telegram with the value 1 disables the
Time
function.
Note
Enabling is only possible via the group object
Disable function Time
.
•
0, i.e., enable function time
: A telegram with the value 0 enables the
Time
function.
Note
If the staircase lighting is disabled when the function
Time
is operational, the light will stay at ON
until it is switched to OFF manually.
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......