![ABB i-bus KNX JRA/S 6.230.3.1 Product Manual Download Page 116](http://html.mh-extra.com/html/abb/i-bus-knx-jra-s-6-230-3-1/i-bus-knx-jra-s-6-230-3-1_product-manual_3075116.webp)
ABB i-bus
®
KNX
Commissioning
114 2CDC506083D0201 | JRA/S 6.230.3.1
No.
Function
Object name
Data type
Flags
87
Status byte
Blind Output A,B
Shutter Output A,B
1-byte
C, R, T
This group object is enabled if the
Extra feedback
parameter is set to
Status byte
in the
A, B: Blind
parameter window.
This group object provides information about the state of the output and the operation. The information is provided in coded
format in a 1 byte value.
The Blind/Roller Shutter Actuator uses this group object to send information concerning the mode in which the output is
currently operating. Only one mode can be activated at any time.
The status byte is sent after a change.
Bit sequence:
76543210
Bit 7:
not used
Always:
0
Bit 6:
not used
Always:
0
Bit 5:
Safety A
Telegram value:
0: inactive
1: active
Bit 4:
Safety B
Telegram value:
0: inactive
1: active
Bit 3:
Automatic
Telegram value:
0: inactive
1: active
Bit 2:
Sun
Telegram value:
0: inactive
1: active
Bit 1:
Upper end position
Telegram value:
0: inactive
1: active
Bit 0:
Lower end position
Telegram value:
0: inactive
1: active
Special coding for bit 0 and bit 1:
Bit sequence 00:
Blind between upper and lower end position
Bit sequence 01:
Lower end position
Bit sequence 10:
Upper end position
Bit sequence 11:
Undefined blind position
For further information see: Blind/shutter status byte, p. 142
88
Status Lower end position
Blind Output A,B
Shutter Output A,B
1 bit
DPT 1.002
C, R, T
This group object is enabled if the
Extra feedback
parameter is set to
End positions
in the
A, B: Blind/Shutter
parameter
window respectively.
This group object defines whether the blind is or is not in the lower end position. The group object value is sent about five
seconds after completion of a movement.
Telegram value:
1 = blind in lower end position.
0 = blind not in lower end position
Note
After a download or ETS reset, the blind/shutter position is unknown and a 1 is sent to the
Status Upper end position
and
Status Lower end position
objects.
Summary of Contents for i-bus KNX JRA/S 6.230.3.1
Page 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Page 2: ......
Page 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Page 142: ......
Page 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Page 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Page 151: ......