ABB i-bus
®
KNX
Commissioning
80 2CDC506083D0201 | JRA/S 6.230.3.1
3.3.3.3
Input a: Dim sensor parameter window
The operation mode allows the operation of dimmable lighting. This parameter window is visible if the
Switch/Dimming sensor
option is selected in the Input a Function parameter window, p. 64.
Enable group object
"Block" 1-bit
Options:
No
Yes
•
Yes:
The 1-bit group object
Block
is enabled. This can be used to disable the input.
Note
If the input is disabled and the option
Send cyclically
is set, the last state is still sent regardless of the
block. The option
Block
still blocks the physical input, sending continues internally.