ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 51
Number of control value inputs
Options:
1
2
This parameter defines the number of control value inputs (communication objects) for automatic opera-
tion.
1
: There is only one
Control value
communication object.
2: There are two communication objects
–
Control value A
and
Control value B
– and the following pa-
rameter appears:
select by...
Options:
Largest value
Communication object "Control value A/B"
This parameter sets how the blower actuator selects which control value (A or B) to use.
Largest value
: The largest control value is always selected. If the values are equal (but
not 0), the input that most recently received a value is selected.
Communication object "Control value A/B":
The control value to use is selected via the
communication object.
Activate monitoring control values
Options:
No
Yes
This parameter sets the monitoring for the control value input(s), which detects any missing telegrams on
the communication object(s).
No
: Control value monitoring is deactivated.
Yes
: Control value monitoring is activated.
With the option
Yes
, the following parameters appear:
Monitoring time
in s [30…65,535]
Options:
0...120...65,535
This parameter sets the maximum time allowed between two telegrams. An error is reported if this
time is exceeded.