ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 25
3.2.2.1.1
Parameter window
- Status messages
(Multi-level)
This is the parameter window where status messages are defined.
This parameter window is always visible for output A. For outputs C, D and E it is visible if the
Outputs C,
D, E
Parameter window Enable outputs A...F
on p.20 is set to
Enable as fans
.
Enable communication objects
"Status Fan speed x" 1 bit
Options:
No
Yes
The setting of a fan speed is displayed via these communication objects. You can parameterize whether or
not the status of a current or required fan speed is displayed.
Yes
: Three 1 bit communication objects,
Status speed x
(x = 1...3) are enabled. The following parame-
ters appear:
Meaning
Options:
Current fan speed
Required fan speed
This parameter defines which status
–
Current fan speed
or
Required fan speed
– is displayed.