ABB i-bus
®
KNX
Start-up
74 2CDC508116D0203 | FCL/S x.6.1.1
No.
Function
Object name
Data type
Flags
21
61
Limitation 1
Fan A
Fan CDE
1 bit
DPT 1.003
C, W
The communication object is enabled if the parameter
Enable limitations
in parameter window
Automatic control
is set to
Yes.
Note
Limitation 1 is only active in automatic operation.
Limitation 1 is active if the communication object
Limitation 1
receives a telegram with the value 1 and deactivated if the same
communication object receives a telegram with the value 0.
When Limitation 1 is activated, the fan can only assume the fan speed or speed range which has been set in the parameter
window
Fan limitation
.
Telegram value:
0 = limitation x inactive
1 = limitation x active
22
62
Limitation 2
See communication object 21
23
63
Limitation 3
See communication object 21
24
64
Limitation 4
See communication object 21
25
65
Forced operation
Fan A
Fan CDE
1 bit
DPT 1.003
C, W
The communication object is enabled if the parameter
Enable communication object "Forced operation" 1 bit
in the
A: Fan
or
CDE: Fan
parameter window is set to
Yes
.
If a forced operation is activated, the device switches to forced operation regardless of the control value and its parameterized
Limitation 1
…4.
Telegram value:
0 = no forced operation
1 = forced operation