![ABB i-bus KNX FCL/S 1.6.1.1 Product Manual Download Page 32](http://html.mh-extra.com/html/abb/i-bus-knx-fcl-s-1-6-1-1/i-bus-knx-fcl-s-1-6-1-1_product-manual_3074032.webp)
ABB i-bus
®
KNX
Start-up
30 2CDC508116D0203 | FCL/S x.6.1.1
3.2.2.1.2
Parameter window
- Automatic control
(Multi-level)
This is the parameter window where you define the threshold values for switchover of the fan speed. Limi-
tations can also be enabled here.
This parameter window is visible if the
Enable automatic operation
parameter in
, p.21 is set to
Yes
.
When automatic operation is enabled, it is active after a download or an ETS reset.
When you activate a communication object in the
Direct operation
parameter window, automatic operation
stops immediately. You can only reactivate it via the
Automatic ON/OFF
communication object.
Important
The device evaluates threshold values in ascending order, i.e. first it checks the threshold value for
Off -
> Fan speed 1
, then
Fan speed 1 -> Fan speed 2
, and so on.
Proper functionality is only assured if the threshold value for
OFF -> Fan speed 1
is less than that for
Fan speed 1 -> Fan speed 2
and this is less than
Fan speed 2 -> Fan speed 3
, etc.
Object value "Automatic On/Off"
switch on to the automatic
Options:
1
0
This parameter defines how to react to a telegram.
1
: Automatic is activated by a telegram with value 1.
0
: Automatic is activated by a telegram with value 0.