ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 75
No.
Function
Object name
Data type
Flags
26
66
Automatic ON/OFF
Fan A
Fan CDE
1 bit
DPT 1.003
C, W
The communication object is enabled if the parameter
Enable automatic operation
in the
A: Fan
or
CDE: Fan
parameter win-
dow is set to
Yes
.
If automatic operation is enabled, it will be activated on this communication object after a download, an ETS reset or receiving
a telegram with the value 1. Automatic operation is switched off if a signal is received on a "manual communication object".
Manual communication objects are:
Fan: Fan speed switch
Fan: Switch speed x (x = 1, 2 or 3)
Fan: Fan speed up/down
Fan: Limitation x (x = 1, 2, 3 or 4)
During one of the four limitations or forced operation, automatic mode remains active but operates only within the allowed
limits.
If the value 1 is set in the parameter:
Telegram value
0 = automatic operation OFF
1 = automatic operation ON
If the value 0 is set in the parameter:
Telegram value
0 = automatic operation ON
1 = automatic operation OFF
27
67
Status Automatic
Fan A
Fan CDE
1 bit
DPT 1.003
C, R, W
The communication object is enabled if the parameter
Enable communication object "Status Automatic" 1 bit
in parameter
window
- Status messages is
set to
Yes.
You can parameterize whether the communication object value is updated but not sent, sent on request, or only sent when
changed.
The communication object indicates the status of automatic operation.
Telegram value:
0 = inactive
1 = activated