ABB i-bus
®
KNX
Start-up
64 2CDC508116D0203 | FCL/S x.6.1.1
CO No.
Function
Name
Data Point
Type (DPT)
Length
Flags
C
R
W T
A
40
Switch
Output B
1,001
1 bit
x
x
41
Permanent ON
Output B
1,003
1 bit
x
x
42
Disable function Time
Output B
1,003
1 bit
x
x
43
Status Switch
Output B
1,001
1 bit
x
x
x
44…49
Not assigned
50
Fan speed switch
Fan CDE (Multi-level)
5,010
1 byte
x
x
Switch
Output C
1,001
1 bit
x
x
51
Switch speed 1
Fan CDE (Multi-level)
1,001
1 bit
x
x
Switch
Fan CDE (One-level)
1,001
1 bit
x
x
Permanent ON
Output C
1,003
1 bit
x
x
52
Switch speed 2
Fan CDE (Multi-level)
1,001
1 bit
x
x
Disable function Time
Output C
1,003
1 bit
x
x
53
Switch speed 3
Fan CDE (Multi-level)
1,001
1 bit
x
x
Status Switch
Output C
1,001
1 bit
x
x
x
54
Fan speed up/down
Fan CDE (Multi-level)
1,007
1 bit
x
x
55
Status fan ON/OFF
Fan CDE
1,001
1 bit
x
x
56
Status Fan speed
Fan CDE (Multi-level)
5,010
1 byte
x
x
x
57
Status Fan speed 1
Fan CDE (Multi-level)
1,001
1 bit
x
x
x
58
Status Fan speed 2
Fan CDE (Multi-level)
1,001
1 bit
x
x
x
59
Status Fan speed 3
Fan CDE (Multi-level)
1,001
1 bit
x
x
x
60
Switch
Output D
1,001
1 bit
x
x
Run-on
Fan CDE (Multi-level)
1,003
1 bit
x
x
61
Limitation 1
Fan CDE
1,003
1 bit
x
x
Permanent ON
Output D
1,003
1 bit
x
x
62
Limitation 2
Fan CDE
1,003
1 bit
x
x
Disable function Time
Output D
1,003
1 bit
x
x
63
Limitation 3
Fan CDE
1,003
1 bit
x
x
Status Switch
Output D
1,001
1 bit
x
x
x
64
Limitation 4
Fan CDE
1,003
1 bit
x
x
65
Forced operation
Fan CDE
1,003
1 bit
x
x
66
Automatic On/Off
Fan CDE
1,003
1 bit
x
x
67
Status Automatic
Fan CDE
1,003
1 bit
x
x
x
68
Status Byte mode
Fan CDE
non DPT
1 byte
x
x
x
69
Control value A
Fan CDE (2 control values)
5,010
1 byte
x
x
Control value
Fan CDE (only 1 control value)
5,010
1 byte
x
x
70
Control value B
Fan CDE (2 control values)
5,010
1 byte
x
x
Switch
Output E
1,001
1 bit
x
x
71
Toggle control value A/B
Fan CDE (2 control values)
1,001
1 bit
x
x
Permanent ON
Output E
1,003
1 bit
x
x
72
Fault control value
Fan CDE
1,005
1 bit
x
x
x
Disable function Time
Output E
1,003
1 bit
x
x
73
Status Switch
Output E
1,001
1 bit
x
x
x
74…79
Not assigned