ABB i-bus
®
KNX
Device technology
FCL/S x.6.1.1 | 2CDC508116D0203 13
2.2
Mounting and installation
The device is a modular installation device for quick installation in the distribution board on 35 mm mount-
ing rails to EN 60 715.
The mounting position can be selected as required.
The electrical connection is implemented using screw terminals. The connection to the bus is implemented
using the supplied bus connection terminal. The terminal assignment is located on the housing.
The device is ready for operation after connection to the bus voltage.
Accessibility of the devices for the purpose of operation, testing, visual inspection, maintenance and repair
must be provided compliant to VDE 0100-520.
Commissioning requirements
To commission the device you need a PC with ETS (ETS3 or higher) and an interface (e.g. KNX) to the
ABB i-bus
®
.
The device is ready for operation after connection to the bus voltage. No additional auxiliary voltage is re-
quired.
Important
The maximum permissible current of a KNX line may not be exceeded.
During planning and installation ensure that the KNX line is correctly dimensioned.
The device features a maximum current consumption of 12 mA (Fan-In 1).
Mounting and commissioning may only be carried out by electrical specialists. The appropriate standards,
guidelines, regulations and specifications for your country should be observed when planning and setting
up electrical installations and security systems for intrusion and fire detection.
Protect the device from damp, dirt and damage during transport, storage and operation.
Only operate the device within the specified technical data!
The device should only be operated in an enclosed housing (distribution board)!
The voltage supply to the device must be switched off before mounting work is performed.
Danger
To avoid dangerous touch voltages which originate through feedback from differing phase conductors,
all poles must be disconnected when extending or modifying the electrical connections.