ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 41
Example: Start-up behavior of a three-speed fan
The illustration shows the reaction in automatic operation with the option
Switch on over fan
speed 3
, if the fan receives the telegram from the OFF state to set
Fan speed 1
.
* The parameter
Minimum dwell period in fan speed in s [0…65,535]
in the parameter window
Automatic control
is only active and programmable if the
Enable automatic operation
parameter in the
Fan
parameter window is
set to
Yes
.
Important
Forced operation remains valid and is taken into account.
The parameterized minimum fan speed dwell time for automatic control is ignored during manual
operation.
The delay time with speed switchover remains active to protect the fan.