ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 63
3.3
Communication objects
Note
As standard, the write flag (with the exception of 1 bit communication objects) is deleted with the com-
munication object values. Thus the communication object value cannot be changed via the bus. If this
function is required, the write flag must be set in ETS.
The communication object value is overwritten with the parameterized value after bus voltage recovery.
3.3.1
Summary of communication objects
CO No.
Function
Name
Data Point
Type (DPT)
Length
Flags
C
R
W T
A
0
In Operation
System
1,002
1 bit
x
x
1
Request status values
General
1,017
1 bit
x
x
2…9
Not assigned
10
Fan speed switch
Fan A
5,010
1 byte
x
x
11
Switch speed 1
Fan A (Multi-level)
1,001
1 bit
x
x
Switch
Fan A (One-level)
1,001
1 bit
x
x
12
Switch speed 2
Fan A (Multi-level)
1,001
1 bit
x
x
13
Switch speed 3
Fan A (Multi-level)
1,001
1 bit
x
x
14
Fan speed up/down
Fan A (Multi-level)
1,007
1 bit
x
x
15
Status fan ON/OFF
Fan A
1,001
1 bit
x
x
16
Status Fan speed
Fan A (Multi-level)
5,010
1 byte
x
x
x
17
Status Fan speed 1
Fan A (Multi-level)
1,001
1 bit
x
x
x
18
Status Fan speed 2
Fan A (Multi-level)
1,001
1 bit
x
x
x
19
Status Fan speed 3
Fan A (Multi-level)
1,001
1 bit
x
x
x
20
Run-on
Fan A (Multi-level)
1,003
1 bit
x
x
21
Limitation 1
Fan A
1,003
1 bit
x
x
22
Limitation 2
Fan A
1,003
1 bit
x
x
23
Limitation 3
Fan A
1,003
1 bit
x
x
24
Limitation 4
Fan A
1,003
1 bit
x
x
25
Forced operation
Fan A
1,003
1 bit
x
x
26
Automatic On/Off
Fan A
1,003
1 bit
x
x
27
Status Automatic
Fan A
1,003
1 bit
x
x
x
28
Status Byte mode
Fan A
non DPT
1 byte
x
x
x
29
Control value A
Fan A (2 control values)
5,010
1 byte
x
x
Control value
Fan A (only 1 control value)
5,010
1 byte
x
x
30
Control value B
Fan A (2 control values)
5,010
1 byte
x
x
31
Toggle control value A/B
Fan A (2 control values)
1,001
1 bit
x
x
32
Fault control value
Fan A
1,005
1 bit
x
x
x
33…39
Not assigned