ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 71
No.
Function
Communication object name
Data type
Flags
28
Status Byte mode
Fan A
Fan CDE
1 byte
non DPT
C, R, T
The communication object is enabled if the parameter
Enable communication object "Status byte mode" 1 byte
in parameter
window
- Status messages
is set to
Yes.
The operating state of the fan can be displayed or sent on the bus via this communication object. You can parameterize
whether the communication object value is updated but not sent, sent on request, or only sent when changed.
Bit sequence:
76543210
Bit 7:
Forced operation
Telegram value:
0: inactive
1: active
Bit 6:
Limitation 1
Telegram value:
0: inactive
1: active
Bit 5:
Limitation 2
Telegram value:
0: inactive
1: active
Bit 4:
Limitation 3
Telegram value:
0: inactive
1: active
Bit 3:
Limitation 4
Telegram value:
0: inactive
1: active
Bit 2:
Thermostat fault
Telegram value:
0: inactive
1: active
Bit 1:
Automatic
Telegram value:
0: inactive
1: active
Bit 0:
Control value
Telegram value:
0: control value A
1: Control value B
For further information see:
Fan status byte, forced/operation