![ABB i-bus KNX FCL/S 1.6.1.1 Product Manual Download Page 52](http://html.mh-extra.com/html/abb/i-bus-knx-fcl-s-1-6-1-1/i-bus-knx-fcl-s-1-6-1-1_product-manual_3074052.webp)
ABB i-bus
®
KNX
Start-up
50 2CDC508116D0203 | FCL/S x.6.1.1
Hysteresis threshold
value in % +/- [0...20 %]
Options:
0…5…20
This sets a hysteresis at which switchover to the next fan speed occurs.
The setting 0 causes immediate switching without hysteresis.
The entered percentage value is directly added to or subtracted from the percentage value of
Threshold
value speed x
. The result is a new upper or lower threshold value.
Switch threshold top (switch on) = threshold value + hysteresis
Switch threshold bottom (switch off) = threshold value - hysteresis
Example: Single-speed fan control with hysteresis
Using hysteresis avoids continual switching caused by fluctuating input signals around the threshold value.
Summary of Contents for i-bus KNX FCL/S 1.6.1.1
Page 1: ...ABB i bus KNX Blower Actuator FCL S x 6 1 1 Product Manual ...
Page 2: ......
Page 8: ......
Page 98: ......
Page 102: ...ABB i bus KNX Appendix 100 2CDC508116D0203 FCL S x 6 1 1 A 4 Notes ...
Page 103: ......