ABB i-bus
®
KNX
Start-up
56 2CDC508116D0203 | FCL/S x.6.1.1
Object value "Switch" on
bus voltage recovery
Options:
Don't write
Write with "0"
Write with "1"
This parameter determines the response of the communication object
Switch
after a bus voltage recovery.
As standard the communication object
Switch
receives the value 0.
Don't write
: After bus voltage recovery, the value 0 is retained in the communication object
Switch
.
The switch state is not re-determined.
Note
Before the very first download (device fresh from the factory), the value before bus voltage failure is
undefined. For this reason, the communication object
Switch
is written with 0 and the contact is open.
Write with 0
: The communication object
Switch
is written with a 0 on bus voltage recovery. The con-
tact position is redefined and set based on the set device parameterization.
Write with 1
: The communication object
Switch
is written with a 1 on bus voltage recovery. The con-
tact position is redefined and set based on the set device parameterization.
Note
Take note of the reaction on bus voltage failure, recovery and download.
The device draws the energy for switching the contact from the bus. After bus voltage is applied, it takes
about ten seconds before sufficient energy is available to switch all contacts simultaneously.
Depending on the transmission and switching delay on bus voltage recovery set in the
General
parame-
ter window, the individual outputs will only assume the desired contact position after this time.
If a shorter time is set, the device will only switch the first contact when sufficient energy is stored in the
device, in order to ensure that enough energy is available to immediately bring all outputs safely to the
required position if there is another bus voltage failure.
Enable function Time
Options:
No
Yes
No
: The parameter window remains disabled and invisible.
Yes
: The
- Time
parameter window appears.
Enabling the
Time
function enables the
-Time
parameter window, where you can undertake further set-
tings.
Note
For a more precise description of the function, see
, p78, No.42.