ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 45
Fan on bus voltage recovery
Options:
Unchanged
OFF
ON
The response of the fan on bus voltage recovery is defined here.
Unchanged
: The fan speed remains the same.
OFF
: The fan is switched off.
ON
: The fan is switched on.
Caution
The blower actuator is supplied ex-works with a default setting (factory default). This ensures that the
fan setting is switched off when the bus voltage is applied to the relay for the first time, preventing any
unintentional switch-on damage to the device during transport, e.g. due to vibration.
It is advisable to apply a bus voltage before connecting the fan in order to assign it a defined switch
state. This eliminates the possibility of an incorrect contact setting destroying the fan.
Enable automatic operation
Options:
No
Yes
Yes
:
Automatic operation
is enabled and Parameter window
pears.
Function Time on ON
Options:
None
Switching delay
Minimum time
This defines the
Time
function on Fan ON.
None
: No
Time
function is executed.
Switching delay
: The fan is switched on after this delay.
Minimum time
: The fan remains ON for at least this time.
With the
Switching delay
option, the following parameters appear:
Time in s [1…65,535 x 0.1]
Options:
1…20…65,535
The fan is switched on after this delay.
With the
Minimum time
option, the following parameters appear:
Time in s [1…65,535]
Options:
1…20…65,535
The fan remains ON for at least this time.