ABB i-bus
®
KNX
Start-up
70 2CDC508116D0203 | FCL/S x.6.1.1
No.
Function
Communication object name
Data type
Flags
25
65
Forced operation
Fan A
Fan CDE
1 bit
DPT 1.003
C, W
The communication object is enabled if the parameter
Enable communication object "Forced operation" 1 bit
in the
A: Fan
or
CDE: Fan
parameter window is set to
Yes
.
If a forced operation is activated, the device switches to forced operation regardless of the control value and its parameter-
ized Limitation 1-4.
Telegram value:
0 = no forced operation
1 = forced operation
26
66
Automatic ON/OFF
Fan A
Fan CDE
1 bit
DPT 1.003
C, W
The communication object is enabled if
Automatic operation
has been enabled in the
A: Fan
or
CDE: Fan
parameter window.
If automatic operation is enabled, it will be activated after a download, an ETS reset or by an ON telegram on this communi-
cation object.
Automatic mode is switched off if a telegram is received on a "manual communication object".
Manual communication objects are:
Fan: Fan speed switch
Fan: Switch speed x (x = 1, 2 or 3)
Fan: Fan speed up/down
Fan: Limitation x (x = 1, 2, 3 or 4)
During forced operation, automatic mode remains active but operates only within the allowed limits.
If the value 1 is set in the parameter:
Telegram value
0 = automatic operation OFF
1 = automatic operation ON
If the value 0 is set in the parameter:
Telegram value
0 = automatic operation ON
1 = automatic operation OFF
27
67
Status Automatic
Fan A
Fan CDE
1 bit
DPT 1.003
C, R, T
The communication object is enabled if the parameter
Enable communication object "Status Automatic" 1 bit
in parameter
window
- Status messages
is set to
Yes.
You can parameterize whether the communication object value is updated but not sent, sent on request, or only sent when
changed.
The communication object indicates the status of automatic operation.
Telegram value:
0 = inactive
1 = activated