ABB i-bus
®
KNX
Start-up
FCL/S x.6.1.1 | 2CDC508116D0203 73
3.3.3.2
Communication objects
Fan One-level
No.
Function
Object name
Data type
Flags
10
50
Not assigned
11
51
Switch
Fan A
Fan CDE
1 bit
DPT 1.001
C, W
The communication object is enabled if the parameter
Fan type
in the
A: Fan
or
CDE: Fan
parameter window is set to
One-
level
.
The fan can be switched on or off with this 1 bit communication object.
Limitations through forced operation or one of the four limitations 1…4 are retained. Automatic operation is disabled. Commu-
nication object
Automatic ON/OFF
reactivates automatic operation.
If several ON telegrams with the value 1 are received, the last value received will be the one used to control the fan. An OFF
command switches the fan off.
Telegram value:
0 = fan OFF
1 = fan ON
12…14
52…54
Not assigned
15
55
Status fan ON/OFF
Fan A
Fan CDE
1 bit
DPT 1.001
C, T
The communication object is enabled if the parameter
Enable communication object "Status fan On/Off" 1 bit
in the
- Status
messages
parameter window is set to
Yes
.
The communication object receives the communication object value 1 (ON), if the fan speed is not equal to zero (OFF). The
value of the communication object is updated and sent when the fan speed is changed.
This communication object thus defines the status of the fan, whether it is switched on or off. It can also be used for control of
a main switch for the fan.
Telegram value:
0 = OFF
1 = ON
Note
Some fans require an ON telegram before you set a fan speed. Using the communication object
Status fan ON/OFF
,
the fan can, for example, be switched on centrally with a switch actuator via the main switch.
16…20
56…60
Not assigned