Page 39
AquaLink
®
M8 | Installation Manual
Page 38
AquaLink
®
M8 | Installation Manual
9.4 DIP Switch Settings for Heat Pump Installation
This table shows how to configure the system for SOLAR PRIORITY or HEAT PUMP PRIORITY.
DIP S2-1 GREEN 10-PIN
TER-
MINAL BAR
RS485 HEAT PUMP
DESCRIPTION
OFF
No sensor installed
Not connected
In this configuration there is no Solar Heating and no
Heat Pump. Extra AUX is available.
OFF
Sensor installed
Not connected
In this configuration there is Solar Heating and there
is Solar Priority. There is no Heat Pump.
OFF
Sensor installed
Connected
In this configuration there is Solar Heating and there
is Solar Priority. There is Heat Pump. There is Heat
Pump Priority.
ON
No sensor installed
Not connected
In this configuration there is no Solar Heating. There
is a mechanically connected Heat Pump. There is
Heat Pump Priority (a limited implementation).
ON
Sensor installed
Not connected
In this configuration there is no Solar Heating. There
is a mechanically connected Heat Pump. There is
Heat Pump Priority (full implementation).
ON
Sensor installed
Connected
In this configuration there is no Solar Heating. There
is an RS485 controlled Heat Pump. There is Heat
Pump Priority.