background image

Page 19

AquaLink

®

 M8  |   Installation Manual

Page 18

AquaLink

®

 M8  |   Installation Manual

W2

W1

4  3  2  1

W2

W1

First Control Panel

Third Control Panel

W2

W1

Second Control Panel

W2

W1

Fourth Control Panel

W2

W1

Back of

OneTouch

PCB

Jumper Location

Figure 27.  Jumper Settings for Multiple OneTouch

TM

 

Control Panels

Section 4.  System Startup
4.1  OneTouch Programming

4.1.1 

Basic Programming

To set a particular piece of equipment to turn on and 

off at predetermined times, highlight MENU/HELP and 

press SELECT (see Figure 28). Highlight PROGRAM 

and press SELECT. Use the UP or DOWN buttons to 

highlight the equipment (for example, filter pump) then 

press SELECT. Follow the on-screen prompts. Use the 

UP or DOWN buttons to pick each number, starting 

with ON hours, press SELECT to enter and move on to 

the next item to change, including picking what day(s) 

the program will run. If you make a mistake, use the 

BACK button to return to a number. If the program is 

already entered, highlight CHANGE PROGRAM and 

step through to the entry that should be corrected.
   A VARIABLE SPEED PUMP can be programmed 

to run at any one of its eight (8) speeds. Power to the 

variable speed pump is switched on/off by a relay, so to 

program the pump you need to set a program time for 

the relay and for any speeds that you wish to run during 

the pumps on cycle. 
     In the example shown below, the variable speed 

pump is used for pool filtration, so it will be powered 

from the FILTER PUMP relay. Therefore to program the 

variable speed pump you must first set a program time 

for the FILTER PUMP relay, then you need to program 

the desired pump speeds to turn on/off during the 

FILTER PUMP cycle. If you do not program any speeds 

to run during the filtration cycle, then by default the 

variable speed pump will run at the POOL speed setting 

during its filtration cycle.
Example: 

1.  The total length of the filtration cycle is to be from 

8am to 5pm. So program the FILTER PUMP to 

turn on at 8am and to turn off at 5pm

2.  To run the variable speed pump at the SPEED3 

setting from 8am to 1pm, highlight and select VSP 

SPD1 PGM, then highlight and select SPEED3, 

program it to turn on at 8am and off at 1pm.

3.  To run the variable speed pump at the SPEED4 

setting from 1pm to 5pm, highlight and VSP SPD1 

PGM, then highlight and select SPEED4, program 

it to turn on at 1pm and off at 5pm.

ON

OFF

DESCRIPTION

FILTER PUMP 8AM

5PM

Total duration of 

filtration cycle

SPEED3

8AM

1PM

Pump runs at the 

SPEED3 setting

SPEED4

1PM

5PM

Pump runs at the 

SPEED4 setting

NOTE

  The following items can be found either in the 

MENU/HELP or in a Sub Menu under SYSTEM 

SETUP.

4.1.2 

Set the Time Menu

MENU/HELP > SET TIME

To set the time, highlight the MENU/HELP and press 

SELECT. Highlight SET TIME and press SELECT. 

Use the UP or DOWN button to set the values. Press 

SELECT to continue.

4.1.3 

Set the Temperature 

1.

  Pool/Spa Combination

MENU/HELP > SET TEMP > POOL or SPA > SET TEMP VALUE

Highlight MENU/HELP and press SELECT. Highlight 

SET TEMP and press SELECT. Use the UP or DOWN 

button to highlight either POOL or SPA and press 

SELECT. Use the UP or DOWN button to increase or 

decrease the temperature and press SELECT. Use the 

BACK button to return to the main screen.

2.

  Pool/Spa Only

MENU/HELP > SET TEMP > TEMP1 > SET TEMP1 VALUE > 

TEMP2 > SET TEMP2 VALUE

Highlight MENU/HELP and press SELECT. Highlight 

SET TEMP and press SELECT (TEMP1 must be 

higher than TEMP2). Press SELECT on TEMP1. Use 

the UP or DOWN button to increase or decrease the 

temperature and press SELECT. 
Highlight TEMP2 and press SELECT (TEMP1 must be 

higher than TEMP2). Use the UP or DOWN button to 

increase or decrease the temperature and press SELECT. 

Use the BACK button to return to the main screen.

3.

  Maintain Temperature 

Содержание AquaLink M8

Страница 1: ...his product read and follow all warning notices and instructions that accompany this product Failure to follow warning notices and instructions may result in property damage personal injury or death I...

Страница 2: ...8 Installation Manual DATE OF INSTALLATION INSTALLER INFORMATION INITIAL PRESSURE GAUGE READING WITH CLEAN FILTER PUMP MODEL HORSEPOWER FILTER MODEL CONTROL PANEL MODEL SERIAL NUMBER NOTES EQUIPMENT I...

Страница 3: ...aults and General Modes 24 4 5 PDA Installation 24 4 6 PDA Handheld Remote System Defaults and General Modes 26 4 7 PDA Handheld Remote On Off Menu 27 4 8 Pool Heat 28 4 9 Spa Heat 28 4 10 Solar Heat...

Страница 4: ...res between 38 C 100 F and 40 C 104 F are considered safe for a healthy adult Lower water temperatures are recommended for young children and when spa use exceeds 10 minutes b Since excessive water te...

Страница 5: ...of a spa or hot tub The use of alcohol drugs or medication can greatly increase the risk of fatal hyperthermia in hot tubs and spas Water temperature in excess of 38 C 100 F may be hazardous to your...

Страница 6: ...mp Sensors Two 2 JVAs for pool spa combo systems 2 2 Electrical Specifications Power Supply 240 VAC 50 Hz 2 5 A Contact Rating Mains Voltage 25 A 3HP 240 VAC 1500 Watts Incandescent Extra Low Voltage...

Страница 7: ...Page 7 AquaLink M8 Installation Manual Dimensions 122...

Страница 8: ...spa consult the Jandy Pro Series Valve Actuator Installation and Operation Manual to ensure that the JVAs are synchronized and rotate properly Please consult the Jandy Valve Plumbing Manual for furthe...

Страница 9: ...Pool Cleaner Plumbing Heater Booster Pump Pool Return Spa Return Spa Make up Check Valve Pool Intake Spa Intake Filter Pump Heater Pool Return Spa Return Non Booster Pump Pool Cleaner Plumbing Spa Mak...

Страница 10: ...a Pump Pool Pump Pool Intake Spa Intake Spa Return Pool Return Pool Filter Spa Filter Check Valve optional Check Valve Optional NOTE When connecting to the AquaLink RS plug the JVAs into the Intake Re...

Страница 11: ...appropriate wire for equipment 3 2 2 Bonding the Power Center Install a bonding lug to the power center enclosure Connect the bond lug using a 8 solid copper core wire to an approved earth ground an...

Страница 12: ...two cables running to each of the red 4 pin connectors on the power center PCB See Figure 7 3 2 4 Wiring the Pentair Pump The Pentair IntelliFlo VF LCD control panel is disabled when communicating wi...

Страница 13: ...cuitry of 120 VAC or greater do not connect to the green 10 pin terminal bar Instead connect the heater to a high voltage relay in the power center and plug the spare relay into the electric heater re...

Страница 14: ...eration Manual Cam Setting Chart for proper settings 3 5 1 JVA Mounting Positions C Remove these four 4 screws for Standard Position A B Common Port Figure 12 Standard Plumbing Water flow into or out...

Страница 15: ...ews Remove Locking Knob and Handle Remove the 4 Large Phillips Head Screws 3 Turn the actuator over to see into the actuator shaft There are four 4 teeth inside of the shaft Align with the smallest sl...

Страница 16: ...s 1 Turn OFF actuator power Unscrew the locking knob by turning the knob counterclockwise Remove the locking knob and valve handle 2 Remove the four 4 Phillips head screws that secure the actuator lid...

Страница 17: ...he power center to the location of the control panel see Figure 10 Sheetrock Surface Mount Box OneTouch PCB Faceplate Figure 22 OneTouch Surface Mount Installation 4 Pull the 4 conductor cable through...

Страница 18: ...onto the back of the OneTouch PCB Place the OneTouch PCB back into the Flush Mount Housing Insert the screws with rubber washers and hand tighten Do not overtighten Snap the faceplate into place This...

Страница 19: ...t the POOL speed setting during its filtration cycle Example 1 The total length of the filtration cycle is to be from 8am to 5pm So program the FILTER PUMP to turn on at 8am and to turn off at 5pm 2 T...

Страница 20: ...P or DOWN button or the PAGE UP or PAGE DOWN button press SELECT when you find the correct name Choose CUSTOM to type in your own names NOTE The Auxiliary labels AIR BLOWER and FILL LINE have an autom...

Страница 21: ...MP SPA PUMP NOT INSTALLED NOT INSTALLED AUX PUMP NOT INSTALLED If the system is not going to control a variable speed pump then leave the application set to NOT INSTALLED If the system is going to con...

Страница 22: ...h S1 1 is ON then the default label for this preset is CLEANER Anytime the cleaner mode is turned on the pump will run at the speed setting of this preset On a combo system if dip switch S1 1 is OFF t...

Страница 23: ...ected On a dual equipment system when a pump is configured as a SPA PUMP the default label for preset 1 is SPEED1 4 3 16 Preset 2 On a dual equipment system when a pump is configured as a SPA PUMP the...

Страница 24: ...tem is in service or time Out mode the system will default to auto In previous firmware versions the system would default to last mode of operation ATTENTION Special Note to Startup Person The AquaLin...

Страница 25: ...ge Raceway 6 Min To Ground Level Blower or Other Equipment Low Voltage Cable High Voltage Raceway Transceiver J Box 8 Min 18 Channel RF Transceiver A 3 Yellow 1 Red 2 Black 4 Green 1 4 6 DETAIL A Figu...

Страница 26: ...he PCB in the Transceiver J box slide the Learn Switch to LEARN ON See Figure 32 6 On the Handheld Remote display screen a prompt will appear with instructions to slide the J box Learn Switch out of L...

Страница 27: ...t on or off The ALL OFF mode will turn off equipment that has been turned on by any means manual or pre programmed This includes any of the heater enables that were on unless in use by the Maintain fu...

Страница 28: ...SELECT Highlight POOL HEAT and press SELECT Use the UP DOWN arrow keys to set the desired temperature and press SELECT EQUIPMENT FILTER PUMP SPA POOL HEAT SPA HEAT SOLAR HEAT AUX 1 AUX 2 AUX 3 MORE O...

Страница 29: ...OFF OFF OFF OFF OFF ON OFF OFF OFF ENA OFF OFF EQUIPMENT FILTER PUMP SPA POOL HEAT SPA HEAT SOLAR HEAT AUX 1 AUX 2 AUX 3 MORE NOTE If no Solar Sensor is installed EXTRA AUX will appear as a menu item...

Страница 30: ...OLAR HEAT POOL LIGHT AUX 2 AUX 3 MORE ON OFF OFF OFF OFF OFF OFF OFF PLEASE WAIT CYCLING TO CHOSEN COLOR SET COLOR ALPINE WHITE SKY BLUE COBALT BLUE CARIBBEAN BLU SPRING GREEN EMERALD GREEN EMERALD RO...

Страница 31: ...ith your installer The speed of a variable speed pump can be adjusted from the EQUIPMENT ON OFF screen In the example below the SPEED PRESET 3 is adjusted to 2750 RPM 4 14 1 To adjust the Variable Spe...

Страница 32: ...F SELECT EQUIPMENT ON OFF ALL OFF ADD PROGRAM DELETE CHANGE CHILL MODEL SENSORS REMOTES ERRORS MODE POOL SPILLOVER COLOR LIGHTS ASSIGN TO AUX SELECT EQUIPMENT SELECT DEVICE SELECT DEVICE SELECT LABEL...

Страница 33: ...F SPA POOL ADD PROGRAM DELETE CHANGE CHILL MODEL SENSORS REMOTES ERRORS SELECT EQUIPMENT SET SPA ONETOUCH ON OFF SPA MODE CLEAN MODE ALL OFF ON OFF EQUIPMENT ON OFF SELECT EQUIPMENT ON OFF ALL OFF ONE...

Страница 34: ...art number and revision letter displayed is for the CPU Board indicating which model System locked up Microprocessor locked Turn off power to the system and turn back on Programs do not run at the cor...

Страница 35: ...Aux 3 Relay Cool Down Normal Spare Aux Pool Mode See Manual Gas Heater 1 2 3 4 5 6 7 8 Note that S1 3 and S1 6 operate with Pool and Spa Combo Only 230 240 VAC Power 10 Amp 10 Amp 10 Amp 10 Amp 10 Am...

Страница 36: ...de switch is pressed the return valve actuator will rotate to spa circulation Because the intake valve actuator does not rotate the spa will fill with water and overflow into the pool NOTE Leave AUX 3...

Страница 37: ...peed filter pump Filter pump circuit becomes High Speed 3 AUX3 any equipment AUX3 Spa Spillover effect Combination controls only 4 Heater cool down operates Heater cool down disabled 5 Normal operatio...

Страница 38: ...pment No change 4 Heater cool down operates Heater cool down disabled 5 Normal operation Factory adjustment when this switch is on tem perature delays are eliminated and solar tem perature is displaye...

Страница 39: ...There is no Heat Pump OFF Sensor installed Connected In this configuration there is Solar Heating and there is Solar Priority There is Heat Pump There is Heat Pump Priority ON No sensor installed Not...

Страница 40: ...ght 2 Light 3 Light Back Light Basement Light Beach Light Bedroom Light Bug Light Cabana Light Color Wheel Light Deck Light Dock Light Drive Light East Light Entry Light Equipment Light Fan Light Fenc...

Страница 41: ...Page 41 AquaLink M8 Installation Manual NOTES...

Страница 42: ...Page 42 AquaLink M8 Installation Manual NOTES...

Страница 43: ...Page 43 AquaLink M8 Installation Manual NOTES...

Страница 44: ...nal S A S U used under license All trademarks referenced herein are the property of their respective owners 2019 Zodiac Pool Systems Inc H0665000 REVB Fluidra Group Australia 219 Woodpark Road Smithfi...

Отзывы: