10.23
ZA-Intern menu
Parameterisation of internal measuring and monitoring functions
Parameter
Designation
Value range
Factory set-
ting
PW_S9
Password for the indication of additional parameter
0
UVW_CHK
De
fi
nition of motor phase checking on start-up
Single:
The motor phases are checked during initial travel once
the frequency inverter has been switched on. If the check is
successful, no further monitoring is performed.
If the examination is incorrect, with each start an examination is
made until a correct examination could be accomplished.
Cont.:
Check is carried out before starting all travel
Off:
Motor phase check is deactivated
Single
Cont
Off
Single
UVW_PEK
Test voltage for motor phase check
1 ... 10 V:
Selection of the test voltage between 1 V and 10 V.
In case of an error the testing voltage is displayed in the error
message.
15 V:
Test voltage 15 V.
f(P):
The testing voltage depends on the nominal voltage of the
motor, which is entered in the menu "Motor name plate". In case
of an error the testing voltage is displayed in the error message.
1 ... 10 V
15 V
f(P)
f(P)
n_ANA
Initialisation value for analogue input in ZAdyn HY
Example:
n_ANA = 3000
analogue input = 0-10 V
10 V = 3000 1/min
1 ... 3300
3000
Original operating instructions
ZAdyn4B 110-180
Parameter list
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
95/200
1
0
P
a
ra
m
e
te
r
lis
t
Содержание ZA dyn 4B 110
Страница 194: ...Original operating instructions ZAdyn4B 110 180 Enclosure R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 194 200 ...
Страница 197: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 197 200 16 Enclosure ...
Страница 198: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 198 200 ...
Страница 199: ...16 Enclosure Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 199 200 ...