15.11
Travel direction counter
The travel direction counter is a down counter which is counting the allowed travel direction changes
with coated ropes. With the travel direction counter the frequency inverter shows an accurately timed
info text when a rope change is necessary.
15.11.1
Parameters for the travel direction counter
For the travel direction counter there are the following parameters, available in the menu
Statistic
.
In order to be able to use all parameters, the password
TD_PWN
must be assigned
fi
rst.
Parameter
Designation
Value range
Factory setting
TD_PWN
New password
A number between 1 and 9999 can be used as a
password
If the password is set to 0, the direction change coun-
ter is deactivated.
0 ... 9999
0 = no password
0
TD_PWC
Displays the password in coded form. If you lose the
password, please contact the manufacturer.
nicht einstellbar
21689
TD_PW
Enter password.
0 ... 9999
0
TD_SET
Initial value of the down counter
0.00 ... 10.00 M
0.00
TD_RST
Restore the counter reading from the absolute value
encoder
On
Off
Off
The current counter readings and the start value for the direction change counter are also available in
the
info menu
on the
TravelDirection
page.
15.11.2
Activating the direction change counter
For using the travel direction counter, the following parameters have to be adjusted.
Statistics
|
-
"
TD_PWN
0
|
-
"
0
*New password
Assign a new password in the
Statistics/TD_PWN
parameter.
If there is already a password existing, you have to enter it to "TD_PW" before it
can be replaced by a new password.
Statistics
TD_PWN 0
->TD_PWC 21689
*Encrypted password
The
Statistics/TD_PWC
parameter indicates the password in coded form.
With the coded password the ZIEHL-ABEGG SE can decode the original pass-
word.
For example if the owner has forgotten it.
Statistics
|
-
"
TD_PW
0
|
-
"
0
*Password entry
Before every change to TD_SET, the previously assigned password must be
entered in the
Statistics/TD_PW
parameter.
Statistics
|
-
"
TD_SET 0
M
|
-
"
0
*Down counter start value
Enter the maximum number of changes of direction in the
Statistics/TD_SET
parameter.
CAUTION!
Attention!
When the ZAdyn4B is replaced, the current counting value of the down counter "TD_CNT"
must be transferred to the new ZAdyn4B!
Original operating instructions
ZAdyn4B 110-180
Special functions
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
176/200
Содержание ZA dyn 4B 110
Страница 194: ...Original operating instructions ZAdyn4B 110 180 Enclosure R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 194 200 ...
Страница 197: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 197 200 16 Enclosure ...
Страница 198: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 198 200 ...
Страница 199: ...16 Enclosure Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 199 200 ...