15.11.6
Resetting the travel direction counter
Information
At the end of the maximum change of direction, the ZAdyn4B is locked and the error
"E950 TD_CNT:
Drive limit"
appears on the display.
To move the cabin into the position for a cable change after locking the frequency inverter, the
ZAdyn4B must be switched off and back on. Then a further run is possible.
After a successful cable change, the password must be entered in the
Statistics
menu and the down
counter set to its new start value:
Statistics
|
-
"
TD_PW
0
|
-
"
0
*Password entry
Enter the current password in the
Statistics/TD_PW
parameter to enable the
down counter value to be reset.
Statistics
|
-
"
TD_SET 0
M
|
-
"
0
*Down counter start value
Enter
“
0
”
in the
Statistics/TD_SET
parameter.
Statistics
|
-
"
TD_PW
0
|
-
"
0
*Password entry
Enter the current password in the
Statistics/TD_PW
parameter.
Statistics
|
-
"
TD_PWN
0
|
-
"
0
*New password
Enter
“
0
”
in the
Statistics/TD_PWN
parameter.
After successfully setting the down counter the number of counter resets
"TD_RES"
is increased by
one.
To display the current value of TD_RES, in the
info menu
on the
TravelDirection
page, press the
key.
Original operating instructions
ZAdyn4B 110-180
Special functions
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
178/200
Содержание ZA dyn 4B 110
Страница 194: ...Original operating instructions ZAdyn4B 110 180 Enclosure R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 194 200 ...
Страница 197: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 197 200 16 Enclosure ...
Страница 198: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 198 200 ...
Страница 199: ...16 Enclosure Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 199 200 ...