X-DCP
DA
DB
0VD
DATA + (A)
DATA - (B)
GND
(1)
(2)
(3)
(4)
DCP connection
()
terminal designation of connector
For more detailed information on DCP, see chapter "Serial communication/DCP (Drive Control &
Position)"
5.14.2
CANopenLift
•
A shielded bus-cable is not needed, but the data wires should be twisted.
•
The wiring is in a linear structure. The individual devices are connected to the main line with short
stub lines.
•
The bus should be terminated with a terminating resistor of 120 - 150 Ohms, at both ends of the
bus.
•
The maximum length of the bus is 200 m and 6 m at the branch lines.
CAUTION!
Attention!
Incorrectly wired connections can destroy the electrical/electronic components.
Electrostatic discharges can be hazardous to the electronic components and lead to errors in the
software.
The bus line is connected via the X-CAN interface of the ZAdyn4B
X-CAN
CL
CH
0VC
CAN High (H)
CAN Low (L)
GND (optional)
(1)
(2)
(3)
(4)
Optionaler
Schirmanschluss
Connection CAN
To activate the terminating resistance, the jumper at terminal J1 must be plugged into the left two pins
(see
fi
g.).
Original operating instructions
ZAdyn4B 110-180
Electrical installation
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
38/200
Содержание ZA dyn 4B 110
Страница 194: ...Original operating instructions ZAdyn4B 110 180 Enclosure R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 194 200 ...
Страница 197: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 197 200 16 Enclosure ...
Страница 198: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 198 200 ...
Страница 199: ...16 Enclosure Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 199 200 ...