Parameter
Designation
Value range
Factory set-
ting
P1P2
Motor temperature monitoring
OFF:
Temperature monitoring deactivated
PTC:
thermistor (PTC according to DIN 44082)
TC:
Thermal circuit breaker
KTY:
Temperature sensor KTY84-130
Off
PTC
TC
KTY
PTC
R_P1P2
Only accessible when P1P2=KTY is parameterised
Resistance value at which the motor temperature monitor re-
sponds
1190 Ohm = 130
°
C motor temperature
500 ... 5000 Ohm
1190
T_ENC
Rotary encoder monitoring
Time starts with an output of the "MB" output signal. If no rotary
encoder input signals occur during this time, the frequency inver-
ter enters error mode
0.5 ... 7.0 s
2.0
T_CO
Debounce time of the motor contactor monitoring
Monitoring time of the contactor interruption. The
fi
nal stage is
switched off when the contactor contacts are open for longer
than the time set in the T_CO parameter. The time T_CO is
active in interruptions during travel, not in a normal stop. Only
accessible when contactor monitor is activated.
0.00 ... 100.0 ms
0.00=Off
10 ms
T_CDLY
Delay contactor monitor
When the contactor monitor is switched on (menu "Monitoring/-
CO") the reply must be available at the contactor monitor input
within the time T_CDLY for the motor contactors to be closed
(start up) or open (stop).
0.5 ... 7.0 s
1.5 s
T_BR
Debounce time for brake monitoring. The input signal is eval-
uated delayed by the time T_BR. Only accessible if the brake
monitoring is activated.
0.01 ... 3.00 s
0.40
S_MB
Maximum distance with MB=Off
If rotary encoder impulses are detected when the digital output
"MB" is switched off, the frequency inverter issues an error
message if the con
fi
gured path is exceeded.
0.10 ... 1.00 m
0.10
I_MAX
Protection against overload current depending on the nominal
current of the motor
If the con
fi
gured value for "I_MAX" is exceeded for the time
"T_I_MAX", the frequency inverter issues an error message.
20 ...180 %
180
T_I_MAX
Overcurrent protection
If the value con
fi
gured in "I_MAX" (I x "I_MAX") is exceeded for
the time "T_I_MAX", the frequency inverter issues an error mes-
sage.
0.3 ... 10.0 s
5.0
MASK1
Error mask 1...5
Suppression of up to
fi
ve error messages through con
fi
guring
the corresponding error number in an error mask
Error no.
0
MASK2
0
MASK3
0
MASK4
0
MASK5
0
Original operating instructions
ZAdyn4B 110-180
Parameter list
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
83/200
1
0
P
a
ra
m
e
te
r
lis
t
Содержание ZA dyn 4B 110
Страница 194: ...Original operating instructions ZAdyn4B 110 180 Enclosure R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 194 200 ...
Страница 197: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 197 200 16 Enclosure ...
Страница 198: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 198 200 ...
Страница 199: ...16 Enclosure Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 199 200 ...