Dimensions [mm]
A
B
C
D
E
F
G
H
L
FEF180KK4D
380
130
180
102
365
350
6.5
M10
450
5.6.2
Allocation of the line reactor-radio interference
fi
lter to the frequency inverter
Inverter
Line reactor
Radio interference
fi
l-
ter
Part no.
ZAdyn4Bx 110
ND110
-
357196
-
FEF180KK4D
357199
ZAdyn4Bx 180
ND180
-
357197
-
FEF180KK4D
357199
5.7
Residual current operated device (RCCB)
Frequency inverters of the ZAdyn type require no FI circuit breaker for operation.
The circuit at the output of the ZAdyn4B is monitored by an electronic short-circuit protection. On
detecting a short-circuit current at the output of the ZAdyn (and thus negligible impedance between
the phase and a body or the protective earth of the circuit, or a protective earth of the operating
medium in the case of an error) the output current is switched off within a time of <20
μ
s. On condition
that the potential equalisation for the ZAdyn and the motor was performed according to the valid
standards (VDE0100-Part 540:2012-06 and DIN EN 50178:1997), this behaviour is suf
fi
cient for the
automatic switch off in case of an error demanded by VDE 06-4100
If an FI circuit breaker is required for special reasons (e.g.
fi
re prevention), an all-current sensitive FI
circuit breaker type B must be used. For maximum operational reliability ZIEHL-ABEGG recommends
the use of an FI circuit breaker with reference fault current of 300 mA for
fi
re prevention according to
regulation VdS 3501.
Information
Please note that even when using a correct type B RCCB, false triggering due to high protective earth
currents (stray current) can still occur and that operation with these protective devices is not possible.
5.8
Control transformer in the mains supply line
CAUTION!
Attention!
When using a control transformer in the power line of the ZAdyn4B, you must connect a capacitor
parallel to the transformer's primary winding (see
fi
g.).
The capacitor is used to prevent an extreme increase in voltage in case the voltage fails in one of the
phases to which the transformer is connected. This voltage increase can lead to destruction of the line
fi
lter. The cause of voltage increases is resonance of the control transformer with the radio-interfer-
ence suppression components, which are always used in frequency inverters.
Original operating instructions
ZAdyn4B 110-180
Electrical installation
R-TBA15_01-GB 2014 Index 005
Part.-No. 00163453-GB
25/200
5
E
le
c
tr
ic
a
l
in
s
ta
l-
la
ti
o
n
Содержание ZA dyn 4B 110
Страница 194: ...Original operating instructions ZAdyn4B 110 180 Enclosure R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 194 200 ...
Страница 197: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 197 200 16 Enclosure ...
Страница 198: ...Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 198 200 ...
Страница 199: ...16 Enclosure Original operating instructions ZAdyn4B 110 180 R TBA15_01 GB 2014 Index 005 Part No 00163453 GB 199 200 ...