9.9.9.3
Group version 1: Two controlled groups
Control group 2 via 0 - 10 V output
Controller Setup
Group 2 ON value
Switch-on value for Group2
Setting range: 0 - 100 %
Factory setting: 50 % *
50 %
Group 2 ON value
Controller Setup
OFF Value Group2
Switch-off value for group2
Setting range: 0 - 100 %
Factory setting: 45 % *
45 %
OFF Value Group2
Controller Setup
nmin at Group2
Minimum Value for Group2
Setting range: 0 - 100 %
Factory setting: 20 % *
20 %
nmin at Group2
*
As long as in IO Setup
“
A Function
”
not programmed to
|
5A
|
, display:
|
- - - -
|
Function
•
Group 1 continuously controlled by the device
’
s
“
Master
”
power unit (
motor connection).
•
Group 2 continuously controlled by a second
“
Slave
”
power unit, this is controlled by the
“
Master
”
by a 0 - 10 V signal. IO Setup: A Function =
|
5A
|
(group control).
Controller
Master
Signal
Controller
Slave
0...100 %
1
2
0...100 %
16.05.2012
v_2nd_group_analog_out.vsd
M
M
Analog
In
Analog
Out
0 – 10 V
Analog
In
5A
Example group 2 via 0 -10 V
F
o
u
t
[
H
z
]
16.05.2012
v_fx_2nd_group_analog_out_diagr.vsd
1
2
3
4
5
6
7
8
9
10
Analog In 1
40
35
30
25
20
15
10
5
2
4
6
8
10
12
14
16
18
20
0...10 V
0...20 mA
10
20
30
40
50
60
70
80
90
100 0...100 % PWM
0
0
0
45
50
Fout Standard
nmin @ G2 = 20 %
1
2
3
4
5
6
7
8
9
1
0
A
n
a
lo
g
O
u
t
[V
]
Fout
@ Analog Out =
5A
Analog Out
=
5A
x1
x
1.
4
1
2
G2 ON = 50 %
G2 OFF = 45 %
Fout:
Output frequency
Analog Out:
Analog output 0 - 10 V
Analog In:
Input signal
G 2 ON:
Group 2 ON value
G2 OFF:
OFF Value Group2
nmin @ G2:
nmin at Group2
Fout Standard:
Output diagram wihout group control
If the setting signal or the control deviation exceeds the switch-on point of group 2, group 1 is reduced
to
“
n-min at Group2
”
. From here on both groups run parallel at maximum power.
If group control is activated (A Function =
|
5A
|
) the gradient of the output curve is automatically
increased by factor 1.4 (gradient without group control = 1).
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
63/123