9.1.2
Speed controller with direct setting by keyboard
1.02
Base setup
1.02
Main menu
Base setup
Setting
Protocol
Base setup
Controller Setup
IO Setup
Base setup
Mode
Mode selection:
1.02
1.02
Mode
Base setup
Number steps
Selection: 0, 1, 2, 3, 4, 5
Factory setting:
0
Number steps: 0
In the factory setting
“
0
”
(without steps) the modulation can be set directly with the
▼
▲
keys (
setting in operation).
Number steps: 1, 2, 3, 4, 5
The modulation value can be assigned to each step. The desired step is set with the
▼
▲
keys (
setting in operation).
The following menus become active depending on the selected step count. (Step not
active =
|
- - - -
|
)
0
Number steps
Base setup
Step 1 value
Setting range: 5 Hz * - 50.0 Hz ** (or Step 2 value)
- - - - -
Step 1 value
Base setup
Step 2 value
Factory setting:
|
- - - -
|
Setting range: Step 1 value - 50.0 Hz ** (or Step 3 value)
- - - - -
Step 2 value
Base setup
Step 3 value
Factory setting:
|
- - - -
|
Setting range: Step 2 value - 50.0 Hz ** (or Step 4 value)
- - - - -
Step 3 value
Base setup
Step 4 value
Factory setting:
|
- - - -
|
Setting range: Step 3 value - 50.0 Hz ** (or Step 5 value)
- - - - -
Step 4 value
Base setup
Step 5 value
Factory setting:
|
- - - -
|
Setting range: Step 4 value - 50.0 Hz **
- - - - -
Step 5 value
*
Minimal setting range depending on setting
“
Shutdown Freq.
”
(
“
Motor Setup
”
).
**
Maximal setting range depending on setting
“
Max. Speed
”
(
“
setting
”
).
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
32/123