9.10.3.2
Inverting analog inputs
“
E1
”
/
“
E2
”
After programming the signal or sensor type, an inversion of the inputs can be carried out.
IO Setup
Factory setting for Inverting inputs =
“
OFF
”
(if input activated) (signal: 0 - 10 V, 0 -
20 mA, 4 - 20 mA).
For activation using inverted default signals or sensors with inverted output signals
proportional to the measurement range, switch inverting to
“
ON
”
(Signal: 10 - 0 V, 20 -
0 mA, 20 - 4 mA).
OFF
E1 Inverting
IO Setup
OFF
E2 Inverting
Example: mode speed controller, setting by external signal
nM
50 %
100 %
Si
0
1
2
3
4
5
6
7
8
9
10
10
9
8
7
6
5
4
3
2
1
0
0
2
4
6
8
10
12
14
16
18
20
20
18
16
14
12
10
8
6
4
2
0
4
5,6
7,2
8,8
10,4
12
13,6 15,2 16,8 18,4
20
20
18,4 16,8 15,2 13,6
12
10,4
8,8
7,2
5,6
4
0 – 10 V
10 – 0 V
0 – 20 mA
20 – 0 mA
4 – 20 mA
20 – 4 mA
Min.
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
11.05.2007
v_invertierung_anlaog_eingaenge.vsd
OFF
OFF
ON
OFF
ON
ON
nM
Motor speed
Si
Signal
OFF
Inverting = OFF
ON
Inverting = ON
9.10.3.3
“
E1
”
/
“
E2
”
Bus mode
After programming the signal or sensor type, the raw value (0-32767) of an analog sensor input can
be written in a Holding Register (h9000 for E1 and h9001 for E2) with the bus mode activated.
The connection is made at the MODBUS RTU Slave interface. Connecting terminals: A (D+), B (D-).
IO Setup
The bus mode of the inputs is set to
“
OFF
”
at the factory.
With activated bus mode, the raw values can be written accordingly into the Holding
Registers, addresses h9000 and h9001 for
“
E1
”
and
“
E2
”
.
OFF
E1 Busmode
IO Setup
OFF
E2 Busmode
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
80/123