![ZIEHL-ABEGG FXDM25 Скачать руководство пользователя страница 82](http://html1.mh-extra.com/html/ziehl-abegg/fxdm25/fxdm25_operating-instructions-manual_3796534082.webp)
12
14
11
22
24
21
K1
K2
11.05.2007
v_relais_k1_k2.vsd
K1
1
= energized, terminals 11-14 bridged
0
= de-energized, terminals 11-12 bridged
K2
1
= energized, terminals 21-24 bridged
0
= de-energized, terminals 21-22 bridged
Function Controller status
K1/ K2
1 = energized
0 = de-energized
Inverting
OFF
ON
1K
Operation without fault, line supply okay
1
0
2K
Fault with indication by relay
0
1
3K
Ext. Fault at digital input for external fault
1
0
4K
Over or falling below limits for modulation
1
0
5K
over or falling below limits for input signal
“
E1
”
1
0
6K
over or falling below limits for input signal
“
E2
”
1
0
7K
setpoint deviation to high
1
0
8K
Activation of second group
1
0
12K
Activation of third group
1
0
13K
Activation of fourth group
1
0
9.10.5
Programming Add-on module type Z-Modul-B
After connecting the module, the menu group
“
IO Setup
”
is followed automatically by the additionmal
menu group
“
IO Extension
”
in which the settings for the inputs and outputs of the module are made.
•
1 x analog input 0 - 10 V. For mode
1.01
without function, starting from
2.01
funktion
|
1E
|
or
|
2E
|
possible.
–
Function
|
1E
|
for external target value function.
–
Function
|
2E
|
for external manual operation.
•
1 x output 0 - 10 V (A2 / GND), Function programmable, e.g., for: Fixed voltage, proportional level
control, proportional input signal, group control, drive 2.
•
3 x digital inputs (D3 / GND, D4 / GND, D5 / GND) function programmable, e.g.: Enable (ON /
OFF), external malfunction, output limitation, input 1/2, target value 1/2, internal/external preset,
controller / manual operation, control-function reversal (
“
heating
”
/
“
cooling
”
).
•
2 x relay outputs (
“
K3
”
and
“
4K
”
) Function programmable, e.g., for: Status signals, alarm indications,
external malfunctions at the digital input, level-control threshold, input signal threshold, offset
threshold (deviation between current and target value), group control.
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
82/123