Base setup
7.1
Mode and signal input
Information
Simple installation is possible through the selection of the preprogrammed mode of operation.
This determines the basic function of the device; factory setting
1.01
= speed controller (activation via
0 - 10 V signal). The controller con
fi
guration is automatically carried out during selection of the
application related mode of operation. The factory presets in accordance with the mode of operation
are based on many years of experience, which is suitable for many applications. Under special
circumstances, these can be individually adapted (
Operating Instructions / Controller Setup:
“
Controller Con
fi
guration
”
).
In modes from
2.01
it is the job of the device to reach and maintain the set setpoint. To do this, the
measured actual value (sensor value) is compared with the set setpoint and the manipulated variable
(modulation) is determined.
Mode
Signal or Sensor
(input)
Function
1.01
Signal: 0 - 10 V, 0 - 20 mA, 4 - 20 mA
Speed controller with input for Setting signal, two step operation
(Factory setting)
1.02
-
Manual speed controller with direct setting by the
▼▲
keys (0 - 100 %
or in 1 - 5 steps)
2.01
*
Sensor KTY81-210 / PT1000 (E1)
Temperature control airconditioning and refrigeration
(preset set-point 20.0
°
C, P-band 5.0 K)
2.02
*
Sensor KTY81-210 / PT1000 (E1)
Temperature control depending on outdoor temperature
(preset set-point 5.0
°
C, - P-band 20.0 K)
2.03
Sensor KTY81-210 / PT1000 (E1)
Temperature control with additional functions (shutter and heating)
2.04
*
1x Sensor KTY81-210 / PT1000 (E1)
1x Sensor KTY81-210 / PT1000 (E2)
Temperature control with two sensors, comparison or average
2.05
*
1x Sensor KTY81-210 / PT1000 (E1)
1x Sensor KTY81-210 / PT1000 (E2)
Temperature control with two sensors differential temperature
3.01
*
Sensor MBG.. (E1)
Pressure control condensers (refrigeration)
3.02
*
Sensor MBG.. (E1)
Pressure control for condensers with input for refrigerant
3.03
*
1x sensor MBG.. (E1)
1x sensor MBG.. (E2)
Pressure control for two circuit condensers
3.04
*
1x sensor MBG.. (E1)
1x sensor MBG.. (E2)
Pressure control for two circuit condensers with input for refrigerant
4.01
*
Sensor DSG.. / MPG.. (E1)
Pressure control for ventilation systems
4.02
1x Sensor DSG.. / MPG.. (E1)
1x Sensor KTY81-210 / PT1000 (E2)
Pressure control depending on outdoor temperature
4.03
1x Sensor DSG.. / MPG.. (E1)
1x BUS RS 485
Pressure control with outdoor temperature-dependent setpoint adap-
tation and activation by MODBUS
5.01
*
Sensor DSG.. / MPG.. (E1)
Volume control (constant) for ventilation systems
5.02
1x Sensor DSG.. / MPG.. (E1)
1x Sensor KTY81-210 / PT1000 (E2)
Volume control with setpoint depending on outdoor temperature
6.01
*
Sensor MAL.. (E1)
Air velocity control e.g. clean room
*
Operation with a second control circuit possible
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Base setup
L-BAL-E212-GB 1451 Index 003