Example for suppression of 2 ranges (Idealized principle diagram)
A
D
P
50 %
50 %
R
0 %
I
S
100 %
I
35 % max
15 % min
09.05.2007
v_ausblendung_prz.vsd
100 %
1
2
A
Modulation
S
Setpoint
R
Pband
D
Speed controller: setting signal
P
P-controller: control deviation
Setting depending on device type in: %, Hz, rpm
Motor Setup
→
Factory setting no suppression active =
“
OFF
”
→
Motor Setup
OFF
Suppression 1
ON
Suppression1
Motor Setup
→
Setting for
“
Range1 min.
”
Setting range:
“
Shutdown Freq.
”
-
“
Range 1 max.
”
→
Motor Setup
- - - -
Range 1 Min.
15 Hz
Range 1 Min.
Motor Setup
→
Setting for
“
Range1 max.
”
Setting range:
“
Range 1 max.
”
-
“
Max. Frequency
”
→
Motor Setup
OFF
Range 1 Max.
35 Hz
Range 1 Max.
Motor Setup
→
Identical procedures for Suppression2 and Sup-
pression3, as far as desired
→
etc.
OFF
Suppression 2
9.13
Timer (Time switch clock) option with Z-Modul-RTC
Main menu
Timer
IO Setup
Limits
Motor Setup
Timer
Diagnostic
9.13.1
Timerfunction
If necessary the clock module type Z-Modul-RTC Part.-No. 380056 can be retro
fi
tted. On the PCB
board is the plug connection
|
X13
|
available.
The device has then a real-time clock. The clock is buffered and has after suf
fi
cient length of time with
voltage supply a 2 - 3 day reserve.
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
94/123