9.4
Pressure control airconditioning
4.01
...
4.03
9.4.1
Base setup
4.01
...
4.03
Main menu
Base setup
Start
Setting
Protocol
Base setup
Controller Setup
Base setup
Mode
Mode selection e.g.
4.01
4.01
Mode
Base setup
E1 Analog In
The sensor input is factory set for modes of group
4
to sensor type
“
DSG200
”
.
Measuring range: 0...200 Pa
Output signal: 0 - 10 V
Connection terminals:
“
E1
”
,
“
GND
”
,
“
24V
”
Other settable sensors / measuring ranges:
•
“
DSG 50
”
,
“
DSG100
”
,
“
DSG200
”
,
“
DSG300
”
,
“
DSG500
”
,
“
DSG1000
”
,
“
DSG2000
”
,
“
DSG4000
”
,
“
DSG6000
”
, INT300, INT500 (numerical data
measuring range [Pa], output signal 0 - 10 V). Type designation DSG...
pressure
sensor with new type designation MPG..
•
0 - 10 V, 0 - 20 mA, 4 - 20 mA (for sensors with free measuring range and linear
characteristic)
The sensor measuring range must be entered for sensors with free measuring range in
order to display the actual value correctly.
Example with a 0 - 10 V sensor and 0 - 400 Pa measurement range:
E1 Analog In = 0 - 10 V, E1 Unit = Pa, E1 Decimals = 1, E1 Min. = 0,0 Pa, E1 Max. =
400 Pa
DSG200
E1 Analog In
Base setup
E1 Offset
Sensor calibration with calibrated comparison device.
The current
“
E1 Actual
”
is displayed including the offset set here.
0.0 Pa
E1 Offset
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
45/123